AC failure bridging time @ Inom | > 20 ms @ 230 V AC / > 20 ms @ 115 V AC |
Degree of efficiency | 93% |
Earth leakage current, max. | 3.5 mA |
Housing version | Metal, corrosion resistant |
Indication | Green LED (Uoutput > 21.6 V DC), Yellow LED (loutput > 90 % IRated typ. ), red LED (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) |
MTBF | According to Standard | SN 29500 | Operating time (hours), min. | 2 Mh | Ambient temperature | 25 °C | Input voltage | 230 V | Output power | 480 W | Duty cycle | 100 % | According to Standard | SN 29500 | Operating time (hours), min. | 904 kh | Ambient temperature | 40 °C | Input voltage | 230 V | Output power | 480 W | Duty cycle | 100 % | | |
Max. perm. air humidity (operational) | 5 %…95 % RH |
Mounting position, installation notice | on terminal rail TS 35 |
Operating temperature | -25 °C...70 °C |
Power factor (approx.) | > 0.98…230 V AC / > 0.98…115 V AC |
Power loss, idling | 5 W |
Power loss, nominal load | 50 W |
Protection against over-heating | Yes |
Protection against reverse voltages from the load | 58…65 V DC |
Protection degree | IP20 |
Short-circuit protection | Yes |