SIEMENS 6ES7322-1BL00-0AA0 SIMATIC S7-300 Digital Output Module

SIEMENS 6ES7322-1BL00-0AA0: SIMATIC S7-300, Digital output SM 322, isolated, 32 DO, 24 V DC, 0.5A, 1x 40-pole, Total current 4 A/group (16 A/module).

Products Details

 
Product
Article Number (Market Facing Number) 6ES7322-1BL00-0AA0
Product Description SIMATIC S7-300, Digital output SM 322, isolated, 32 DO, 24 V DC, 0.5A, 1x 40-pole, Total current 4 A/group (16 A/module)
Product family SM 322 digital output modules
Product Lifecycle (PLM) PM300:Active Product
PLM Effective Date Product phase-out since: 01.10.2023
Delivery information
Export Control Regulations AL : N / ECCN : 9N9999
Standard lead time ex-works 85 Day/Days
Net Weight (kg) 0,309 Kg
Packaging Dimension 12,80 x 15,20 x 5,00
Package size unit of measure CM
Quantity Unit 1 Piece
Packaging Quantity 1
Additional Product Information
EAN 4025515060932
UPC 040892560664
Commodity Code 85389091
LKZ_FDB/ CatalogID ST73
Product Group 4031
Group Code R151
Country of origin Germany
    
Supply voltage
Load voltage L+  
• Rated value (DC) 24 V
• permissible range, lower limit (DC) 20.4 V
• permissible range, upper limit (DC) 28.8 V
Input current  
from load voltage L+ (without load), max. 160 mA
from backplane bus 5 V DC, max. 110 mA
Power loss  
Power loss, typ. 6.6 W
Digital outputs  
Number of digital outputs 32
Short-circuit protection Yes; Electronic
• Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-53 V)
Controlling a digital input Yes
Switching capacity of the outputs  
• on lamp load, max. 5 W
Load resistance range  
• lower limit 48 Q
• upper limit 4 kQ
Output voltage  
• for signal "1", min. L+ (-0.8 V)
Output current  
• for signal "1" rated value 0.5 A
• for signal "1" permissible range for 0 to 40 °C, min. 5 mA
• for signal "1" permissible range for 0 to 40 °C, max. 0.6 A
• for signal "1" permissible range for 40 to 60 °C, min. 5 mA
• for signal "1" permissible range for 40 to 60 °C, 0.6 A
max.  
• for signal "1" minimum load current 5 mA
• for signal "0" residual current, max. 0.5 mA
Output delay with resistive load  
• "0" to "1", max. 100 卩s
• "1" to "0", max. 500 卩s
Parallel switching of two outputs  
• for uprating No
• for redundant control of a load Yes; only outputs of the same group
Switching frequency  
• with resistive load, max. 100 Hz
• with inductive load, max. 0.5 Hz
Load voltage L+
• Rated value (DC) 24 V
• permissible range, lower limit (DC) 20.4 V
• permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 15 mA
Power loss
Power loss, typ. 6.5 W
Digital inputs
Number of digital inputs 32
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
—up to 40 °C, max. 32
—up to 60 °C, max. 16
vertical installation
—up to 40 °C, max. 32
Input voltage
• Type of input voltage DC
• Rated value (DC) 24 V
• for signal "0" -30 to +5 V
• for signal "1" 13 to 30V
Input current
• for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
—parameterizable No
—at "0" to "1", min. 1.2 ms
—at "0" to "1", max. 4.8 ms
—at "1" to "0", min. 1.2 ms
—at "1" to "0", max. 4.8 ms
Cable length
• shielded, max. 1 000 m
• unshielded, max. 600 m
Encoder
Connectable encoders
• 2-wire sensor Yes
—permissible quiescent current (2-wire sensor),

1.5 mA

max.
 
 
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 260 g
 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours